| Order Code | Description | ||
|---|---|---|---|
| NLP/1-K | Module, single cell battery and charge LED indicator for 6-55 Volt LED loads | ||
| Suitable for mounting inside the luminaire | |||
| NLP/1S/80-K | Module, three cell battery and charge LED indicator for 6-80V LED loads | ||
| Suitable for mounting inside the luminaire |
| NLP/1NLP/1S/80 | |
| LED Voltage Range | 6-55V 6-80V |
| I Rated | 323mA – 40mA385mA – 32mA |
| P Rated | 2.2W2.6W |
| LED Voltage Limit | 55V80V |
| Battery Discharge Current | 900mA1A |
| Mains Supply | 230-240V AC 50/60Hz |
| Power Rating – Charging | 2.7W 17mA λ = 0.67 |
| Power Rating – Standby * | 1.2W 13mA λ = 0.40 |
| Charge Current | 225mA nominal |
| Recharge Period | 24-hours |
| Battery Pack | 3.2V 3.8Ah LiFePO43.2V 4.8Ah LiFePO4 |
| Battery Cut Off | 2.5V |
| Ambient Temperature (Ta) | Battery and Module 5-35°C |
| Case Temperature (Tc) | Battery 5-55°C, Module 5-70°C |
| Integral Module Size | 178mm x 30mm x 22.5mm FC=172mm |
*Following its initial charge, the NLP/1 and NLP/1S will spend 90% of its operational life in standby mode.